ICT Product Distribution > Environment Monitoring System > E-2D / E-5D / E-16D (-16DEL) > Compatible Sensors > Environmental Sensors > Spot Leak Detectors
Environmental Sensors for E-2D/5D/16D/16DEL
Spot Leak Detectors
Spot Liquid Detector, Point Leak Detection Sensor
Product Code: E-LD-SPDT
- For detecting water presence and warning of flooding.
- Features gold-plated probes and microchip technology for dependable detection of conductive liquids.
- SPDT alarm contacts
- Weatherproof enclosure
- LEDs for power and alarm indication
- Ideal solution for sensing leaks under a raised computer floor or air conditioning drip pans.
- Use in large-scale network control centers, data centers, server rooms/closets, unattended remote shelters, mechanical equipment rooms, sensitive areas with overhead piping, industrial process control rooms, etc.
- Adjustable detection level.
- Probe height adjustable 0″ to 1.5″ (0 to 38mm)
- Current consumption: 10mA typical, 30mA maximum @ 12VDC.
- Maximum cable length: 1000 ft (305m)
- Dimensions WxDxH: 3.75×4.5×4.23 in (95x114x107 mm)
- Powered by E-2D/5D/16D.
- Regulatory approvals: CE
NTI Part # | Description |
---|---|
E-LD-SPDT | Spot Liquid Detector, Point Leak Detection Sensor |
Compact-Size Spot Liquid Detector, Point Leak Detection Sensor
Product Code: E-SLDO-14
- Use to detect fluids in confined areas, such as condensation drip pans.
- SPDT alarm contacts
- One generic relay output
- No exposed metal sensing posts – nothing to rust or corrode
- Potted electronics — functions when submerged in water
- Adjustable detection level.
- Probe height adjustable 0″ to 0.75″ (0 to 19mm)
- Dimensions WxDxH: 1.55×1.0x2.0 in (39x25x51 mm)
- Cable length: 14 feet
- E-SLDO-14 includes 24V/0.5A US power supply.
- E-SLDO-14-240VTR includes 240/208/120 to 24 VAC power transformer and country-specific line cord.
- Regulatory approvals: CE, RoHS
NTI Part # | Description |
---|---|
E-SLDO-14 | 24V/0.5A US power supply |
E-SLDO-14-240VTR | 240/208/120 to 24 VAC power transformer and country-specific line cord |
Spot Liquid Detector with Built-In Visual & Audible Alarm
Product Code: E-SLDO-A
- Use to detect conductive fluids in confined areas
- Place the sensor on a flat surface under HVAC equipment, dishwashers, washing machines, refrigerators, compressors, or electrical switchgear rooms and other potential leakage areas.
- Water level detection range: 0.03 to 0.53″ (0.79 to 13 mm).
- DPDT alarm contacts.
- Audible alarm signal: 85 dB at 1 foot distance.
- Red LED for visual alarm signal.
- Green LED for power
- Current consumption: 30mA typical, 85mA maximum @ 12VDC.
- Dimensions WxDxH: 2×4.13×0.19 in (51x105x30 mm).
- Includes adjustable mounting bracket attached via adhesive strips or two screws.
- Operating temperature: 32 to 122°F (0 to 50°C).
- Powered by E-2D/5D/16D.
- Cable length: 4.9 ft (1.5 m)
- Regulatory approvals: CE, RoHS.
NTI Part # | Description |
---|---|
E-SLDO-A | Spot Liquid Detector with Built-In Visual & Audible Alarm |
IP68 Submersible Spot Liquid Detector
Product Code: E-SLDO-IP68
- Use to detect conductive fluids in confined areas
- Place the sensor on a flat surface under HVAC equipment, dishwashers, washing machines, refrigerators, compressors, or electrical switchgear rooms and other potential leakage areas.
- Water level detection range: 0.03 to 0.53″ (0.79 to 13 mm).
- DPDT alarm contacts.
- Red LED for visual alarm signal.
- Green LED for power
- Current consumption: 30mA typical, 85mA maximum @ 12VDC.
- Dimensions WxDxH: 2×4.13×0.19 in (51x105x30 mm).
- Includes adjustable mounting bracket attached via adhesive strips or two screws.
- Operating temperature: 32 to 122°F (0 to 50°C).
- Powered by E-2D/5D/16D.
- Cable length: 4.9 ft (1.5 m)
- Enclosure rating: NEMA 6P (IP68) submersible.
- Max submersion depth: 1 meter
- Max submersion time: 2 hours
- Regulatory approvals: CE, RoHS.
NTI Part # | Description |
---|---|
E-SLDO-IP68 | IP68 Submersible Spot Liquid Detector |
Outdoor Oil Leak Detection Sensor
Product Code: E-SOD-3M
- Use to detect oil or non-conductive liquids in outdoor locations or in areas that are susceptible to leaks.
- The sensor includes two liquid detectors; one looking for conductive liquids (e.g. water), and the other looking for non-conductive liquids (e.g. fuel oil, diesel fuel).
- When there is no water but oil/non-conductive liquid present, an alarm will trigger.
- If there is water present but no existing non-conductive liquid leak alarm, the sensor will not activate until the water is removed.
- Refer to the datasheet for further details on the conductive and non-conductive detection interaction.
- Minimum puddle depth: 0.04-0.08″ (1-2 mm).
- Normally-open alarm contact.
- IP 65 rated.
- Dimensions excluding bracket DxH (in): 1.50×2.95 (38×75 mm).
- Cable length: 9.84 ft (3 m).
- Contact an NTI product consultant for custom cable lengths up to 1000 ft (305m).
- Operating temperature: -4 to 167°F (-20 to 75°C).
- Powered by E-2D/5D/16D.
- Current consumption: 30mA @ 24VDC.
- Material: ABS plastic.
- Regulatory approvals: CE, RoHS.
NTI Part # | Description |
---|---|
E-SOD-3M | Outdoor Oil Leak Detection Sensor |
All Products In This Category
ENVIROMUX
ENVIROMUX-2D
Small Enterprise Environment Monitoring System
ENVIROMUX-5D
Medium Enterprise Environment Monitoring System
ENVIROMUX-16D/-16DEL
Large Enterprise Environment Monitoring System
ENVIROMUX-MICRO-T/-TRHP
Micro Environment Monitoring System
ENVIROMUX-MINI-LXO
Mini Environment Monitoring System
ENVIROMUX-1W
Low-Cost Environment Monitoring System
E-MNG-SH
Self-Hosted Enterprise Environment Monitoring System Management Software
E-MNG-xxxx
Management Software for Enterprise Environment Monitoring Systems – Client/Server Architecture
SPDU-S2
Secure Remote Power Control Unit with Environmental Monitoring
PWR-RMT-RBT-LC
Low-Cost Remote Power Reboot Switch with IEC320 C13 Outlet
PWR-RMT-RBT2-515R-LCV2
Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets
PWR-RMT-RBT2-515R-LCV2
Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets