Digital Input/Output Expander (Open-Collector Outputs)

Product Code: E-DI16DO16

 

  • Adds 16 digital inputs and 16 digital open-collector outputs to the E-2D/5D/16D
    • Interfaces with the E-2D/5D/16D via the RJ45 Sensor Port
      • Each E-16D supports up to 16 E-DI16DO16.
      • Each E-5D supports up to five E-DI16DO16.
      • Each E-2D supports up to two E-DI16DO16.
  • Digital inputs:
    • 16 screw terminal pairs for connecting dry contact devices
      • One screw terminal pair for tachometer; 0 to 255 Hz
    • Accepts 26 to 16AWG wire
    • Potential free
    • Voltage range: 0 to +36VDC
    • Over-voltage surge protected
  • Digital outputs:
    • 16 screw terminal pairs for open-collector outputs
    • Accepts 26 to 16AWG wire
    • Rated sink current: 500 mA per output
    • +5VDC, 22kΩ pull-ups
    • Voltage range: 0 to +24VDC
    • Over-voltage surge protected
  • Supports CAT5/5e/6 cable up to 500 ft. (152.4 m)
  • Control via SNMP:
    • Requires read-write community configuration.
    • Digital inputs are fixed values (not writable) while open-collector outputs are writable.
    • Locate OIDS using a MIB browser.
  • Powered by E-2D/5D/16D.
  • Compatible with E-2D/5D/16D.
  • Optional DIN mounting available.
  • Dimensions WxDxH: 6.49×3.10×1.08 in (165x79x27 mm)
  • Regulatory approvals: RoHS
  • Operating temperature: 32 to 158°F (0 to 70°C)
  • Storage temperature: -4 to 158°F (-20 to 70°C)
  • Compatible with E-FSC Fiber Converter/Extender.
    • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
    NTI Part # Description
    E-DI16DO16 Digital Input/Output Expander, Open-Collector Outputs
    E-DI16DO16-D Digital Input/Output Expander, Open-Collector Outputs, DIN Mount

     

    Digital Input/Output Expander (Normally-Open Relay Contact Outputs)

    Product Code: E-DI16DOR16-V2

     

    • Adds 16 digital inputs and 16 digital normally-open relay contact outputs to the E-2D/5D/16D
      • Interfaces with the E-2D/5D/16D via the RJ45 Sensor Port
        • Each E-16D supports up to 16 E-DI16DOR16-V2.
        • Each E-5D supports up to five E-DI16DOR16-V2.
        • Each E-2D supports up to two E-DI16DOR16-V2.
    • Digital inputs:
      • 16 screw terminal pairs for connecting dry contact devices
        • One screw terminal pair for tachometer; 0 to 255 Hz
      • Accepts 26 to 16AWG wire
      • Potential free
      • Voltage range: 0 to +36VDC
      • Over-voltage surge protected
    • Digital outputs:
      • 16 screw terminal pairs for normally-open relay contact outputs
      • Accepts 26 to 16AWG wire
      • Potential free
      • Rated switching load: 0.5A @ 125VAC, 1A @ ±30VDC, 0.5A @ ±48VDC.
      • Galvanic isolation: 1kV
      • Fused
    • Supports CAT5/5e/6 cable up to 500 ft. (152.4 m)
    • Control via SNMP:
      • Requires read-write community configuration.
      • Digital inputs are fixed values (not writable) while output relays are writable.
      • Locate OIDS using a MIB browser.
    • Includes 5V/3A power supply.
    • Current consumption: 75mA @ 5VDC
    • Compatible with E-2D/5D/16D.
    • Available options: desktop unit with wall mounting brackets, DIN mount unit, 1RU rackmount unit, dual side-by-side rackmount units in 1RU.
    • Dimensions WxDxH:
      • E-DI16DOR16-V2 (desktop): 6.49×3.15×1.71 in (165x80x44 mm)
      • E-DI16DOR16-V2R (1RU rackmount) and E-DI16DOR16-V22R (1RU dual side-by-side rackmount): 19×3.15×1.71 in (486x80x44 mm)
    • Regulatory approvals: RoHS
    • MTBF: 650,166 hrs
    • Operating temperature: 32 to 158°F (0 to 70°C)
    • Storage temperature: -4 to 158°F (-20 to 70°C)
    • Compatible with E-FSC Fiber Converter/Extender.
      • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
      NTI Part # Description
      E-DI16DOR16-V2 Digital Input/Output Expander, Normally-Open Relay Contact Outputs, Desktop
      E-DI16DOR16-V2-D Digital Input/Output Expander, Normally-Open Relay Contact Outputs, DIN Mount
      E-DI16DOR16-V2R Digital Input/Output Expander, Normally-Open Relay Contact Outputs, 1RU Rackmount
      E-DI16DOR16-V22R Digital Input/Output Expander, Normally-Open Relay Contact Outputs, 1RU Dual Side-by-Side Rackmount

       

      All Products In This Category

      ENVIROMUX

      ENVIROMUX-2D

      Small Enterprise Environment Monitoring System

      ENVIROMUX-5D

      Medium Enterprise Environment Monitoring System

      ENVIROMUX-16D/-16DEL

      Large Enterprise Environment Monitoring System

      ENVIROMUX-MICRO-T/-TRHP

      Micro Environment Monitoring System

      ENVIROMUX-MINI-LXO

      Mini Environment Monitoring System

      ENVIROMUX-1W

      Low-Cost Environment Monitoring System

      E-MNG-SH

      Self-Hosted Enterprise Environment Monitoring System Management Software

      E-MNG-xxxx

      Management Software for Enterprise Environment Monitoring Systems – Client/Server Architecture

      SPDU-S2

      Secure Remote Power Control Unit with Environmental Monitoring

      PWR-RMT-RBT-LC

      Low-Cost Remote Power Reboot Switch with IEC320 C13 Outlet

      PWR-RMT-RBT2-515R-LCV2

      Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets

      PWR-RMT-RBT2-515R-LCV2

      Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets