ICT Product Distribution > Environment Monitoring System > E-2D / E-5D / E-16D (-16DEL) > Compatible Sensors > Environmental Sensors > Leak Location Detection Sensors
Environmental Sensors for E-2D/5D/16D/16DEL
Leak Location Detection Sensors
Addressable Leak Detection Sensor
Product Code: E-ALDS
- Monitors up to 4,000 feet of E-LDDC-x Liquid Location Detection Sensor Cable.
- Detects the specific location of liquid presence.
- If multiple leaks are occurring at the same time, you will receive notification of the location for the leak closest to E-ALDS. Once that leak is cleared, you will receive notification of the next leak closest to the E-ALDS. This will continue until all leaks are cleared.
- Detects if there is a break in the cable.
- Detects the specific location of liquid presence.
- Supports up to 1,000 feet of E-4WNSC-x non-sensing cable.
- Leak location accuracy:
- 20 to 1,500 feet: ±(1ft + 0.5% of sensing cable length).
- 1,500 to 4,000 feet: ±1% of sensing cable length.
- Built-in Piezo buzzer emits loud beeps to alert personnel.
- Output level: 70dB at 1 foot
- Max current consumption: 13mA @ 5VDC, 18mA@12VDC
- Powered by E-2D/5D/16D.
- Compatible with E-2D/5D/16D.
- Interfaces with the E-2D/5D/16D via the RJ45 sensor port
- Extend up to 500 feet from the E-2D/5D/16D
- M12 4-pin connector for connecting E-LDDC-x Liquid Location Detection Sensor Cable or E-4WNSC-x Non-Sensing Cable
- Dimensions WxDxH: 3.21×2.5×1.22 in (82x64x31 mm)
- Operating temperature: 32 to 158°F (0 to 70°C).
- Regulatory approvals: CE, RoHS
- Integrated mounting brackets for easy surface/wall mounting.
- Use the included terminator at the end of the E-LDDC-x Liquid Location Detection Sensor Cable
- If the terminator is not used, the system will register a cable break.
NTI Part # | Description |
---|---|
E-ALDS | Addressable Leak Detection Sensor |
Liquid Location Detection Sensor Cable
Product Code: E-LLDC-xx
- For detecting water presence at a specific location.
- 100% waterproof electronics.
- Detects any conductive liquid.
- Minimum puddle: 0.6″ (15 mm) diameter.
- Detects liquid depth >0.1″ (2.5 mm).
- M12 4-pin connectors.
- Available lengths: 10/25/50/100 feet and custom lengths up to 4,000 feet.
- Contact an NTI product consultant for custom cable lengths
- Bend radius: 0.375″ (9.53 mm)
- Operating temperature: 32 to 167°F (0 to 75°C).
- Regulatory approvals: CE, RoHS
- MTBF: 10,869,188 hrs
- Compatible with E-ALDS Addressable Leak Detection Sensor.
- Use self-adhesive clips (E-CLPxx-LD) to prevent sensor rope cable from shifting after installation
NTI Part # | Description |
---|---|
E-LLDC-10 | Liquid Location Detection Sensor Cable, 10 feet |
E-LLDC-25 | Liquid Location Detection Sensor Cable, 25 feet |
E-LLDC-50 | Liquid Location Detection Sensor Cable, 50 feet |
E-LLDC-100 | Liquid Location Detection Sensor Cable, 100 feet |
E-CLP10-LD | Self-Adhesive Clips for Liquid Sensor Rope, 10-pack |
E-CLP100-LD | Self-Adhesive Clips for Liquid Sensor Rope, 100-pack |
4-Wire Non-Sensing Cable
Product Code: E-4WNSC-xx
- For use in areas where E-LLDS-xx sensing cable is not required.
- Available lengths: 10/25/50/100 feet and custom lengths up to 1,000 feet.
- Contact an NTI product consultant for custom cable lengths
- M12 4-pin connectors.
- 22 AWG stranded bare copper conductors.
- Color-coded plenum-grade PVC insulation.
- Plenum-grade PVC jacket.
- Cable diameter: 0.136 in
- Operating temperature: 14 to 140°F (-10 to 60°C)
- Will ship in either white or gray.
- Regulatory approvals: CE, RoHS
- Compatible with E-ALDS Addressable Leak Detection Sensor and E-LLDC-xx Liquid Location Detection Sensor Cables.
NTI Part # | Description |
---|---|
E-4WNSC-10 | 4-Wire Non-Sensing Cable, 10 feet |
E-4WNSC-25 | 4-Wire Non-Sensing Cable, 25 feet |
E-4WNSC-50 | 4-Wire Non-Sensing Cable, 50 feet |
E-4WNSC-100 | 4-Wire Non-Sensing Cable, 100 feet |
All Products In This Category
ENVIROMUX
ENVIROMUX-2D
Small Enterprise Environment Monitoring System
ENVIROMUX-5D
Medium Enterprise Environment Monitoring System
ENVIROMUX-16D/-16DEL
Large Enterprise Environment Monitoring System
ENVIROMUX-MICRO-T/-TRHP
Micro Environment Monitoring System
ENVIROMUX-MINI-LXO
Mini Environment Monitoring System
ENVIROMUX-1W
Low-Cost Environment Monitoring System
E-MNG-SH
Self-Hosted Enterprise Environment Monitoring System Management Software
E-MNG-xxxx
Management Software for Enterprise Environment Monitoring Systems – Client/Server Architecture
SPDU-S2
Secure Remote Power Control Unit with Environmental Monitoring
PWR-RMT-RBT-LC
Low-Cost Remote Power Reboot Switch with IEC320 C13 Outlet
PWR-RMT-RBT2-515R-LCV2
Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets
PWR-RMT-RBT2-515R-LCV2
Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets