ICT Product Distribution > Environment Monitoring System > E-MICRO > Compatible Sensors > Environmental Sensors > Gas Detection Sensors
Environmental Sensors for E-MICRO
Gas Detection Sensors
Carbon Monoxide Detector, CO
Product Code: E-CMD-P
- Continuous air monitoring.
- Pre-set alarm points alert at:
- 70 ppm after 60 to 240 minutes
- 150 ppm after 10 to 50 minutes
- 400 ppm after 4 to 15 minutes
- Flush or surface mount.
- Test functionality of electrochemical CO sensing cell.
- Connect to RJ45 or digital input sensor ports.
- Screw terminal
- To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-terminated end to the sensor screw terminal.
- Maximum cable length: 1000 ft (305m)
- LED indicators for operation status and system test.
- Current consumption: 40mA @ 12VDC.
- Powered by E-2D/5D/16D.
- Regulatory approvals: UL
NTI Part # | Description |
---|---|
E-CMD-P | Carbon Monoxide Detector, CO |
Gas Detector — Methane, Butane, Propane
Product Code: E-GD-MBP-P
- Use to detect leaks of combustible gas (methane, propane, butane, acetylene, etc.)
- Choose between two levels of detection:
- First level:
- Detects methane at concentrations in excess of 0.5%.
- Detects propane/iso-butane at concentrations in excess of 0.3%.
- Second level:
- Detects methane at concentrations in excess of 0.8%.
- Detects propane/iso-butane at concentrations in excess of 0.5%.
- First level:
- Continuous air monitoring.
- Audible alarm signal: 94 dB at 1 foot.
- Relay specifications: level selectable, normally open or normally closed, 250V AC, max 5A.
- Maximum cable length: 1000 ft (305m)
- Powered by E-2D/5D/16D.
- Current consumption: 150mA @ 12VDC.
- Regulatory approvals: CE
NTI Part # | Description |
---|---|
E-GD-MBP-P | Gas Detector — Methane, Butane, Propane |
Hydrogen Gas Detector
Product Code: E-H2-P
- Use to detect leaks of hydrogen gas in battery monitoring/charging rooms, substations, uninterruptible power supplies (UPS), and hydrogen fueled back-up power systems.
- Alarm set point: 10% LEL hydrogen gas.
- SPDT Alarm and normally-closed output relay.
- Self-restoring or latching options.
- Sensor requires no maintenance or recalibration.
- Includes mounting hardware.
- Voltage supply: 12 to 24 VDC or VAC.
- Can be powered by the E-2D/5D/16D at 12VDC.
- Current consumption: 70mA @ 12VDC.
- Operating temperature: 32 to 120°F (0 to 49°C).
- Dimensions WxDxH (in): 4.5x5x1.63 (114x127x41 mm).
- Powered by E-2D/5D/16D.
NTI Part # | Description |
---|---|
E-H2-P | Hydrogen Gas Detector |
All Products In This Category
ENVIROMUX
ENVIROMUX-2D
Small Enterprise Environment Monitoring System
ENVIROMUX-5D
Medium Enterprise Environment Monitoring System
ENVIROMUX-16D/-16DEL
Large Enterprise Environment Monitoring System
ENVIROMUX-MICRO-T/-TRHP
Micro Environment Monitoring System
ENVIROMUX-MINI-LXO
Mini Environment Monitoring System
ENVIROMUX-1W
Low-Cost Environment Monitoring System
E-MNG-SH
Self-Hosted Enterprise Environment Monitoring System Management Software
E-MNG-xxxx
Management Software for Enterprise Environment Monitoring Systems – Client/Server Architecture
SPDU-S2
Secure Remote Power Control Unit with Environmental Monitoring
PWR-RMT-RBT-LC
Low-Cost Remote Power Reboot Switch with IEC320 C13 Outlet
PWR-RMT-RBT2-515R-LCV2
Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets
PWR-RMT-RBT2-515R-LCV2
Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets