E-16D/-16DEL
Large Enterprise Environment Monitoring System
Monitor and manage server room environmental and security conditions over IP. Provides early warnings before critical events turn into disaster.
Also known as: Remote SNMP Environment Monitoring System, EMS, monitor networking closets, server room alert, IP temperature sensor, humidity sensor, computer room humidity probe.
Product Code: E-16D/-16DEL ( also known as ENVIROMUX-16D/-16DEL )
Warranty: 12 month Standard Warranty
The ENVIROMUX® Enterprise Environment Monitoring System (EMS) monitors critical environmental conditions, such as temperature, humidity, liquid water presence, power, intrusion, and smoke. When a sensor goes out of range of a configurable threshold, the system will notify you via email, LEDs, alarm beacon, siren, web page, network management (SNMP), voice phone calls (via Automatic Voice Dialer System), and SMS messages (via email-to-SMS or external USB modem).
The system includes three internal sensors: temperature, humidity and power. It also supports 16 external configurable sensors, eight digital input sensors, and four output relays for control of external devices.
- Monitor and manage server room environmental and security conditions over IP.
- Sensors supported by a single E-16D:
- 16 external configurable sensors
- 8 digital inputs sensitive to contact closure
- 3 internal sensors – temperature, humidity, power
- 8 Remote Temperature/Humidity Sensors over IP
- E-MICRO-TRH(P): 1 integrated temperature/humidity combination sensor, 2 RJ45 ports for external temperature/humidity sensors, 2 digital inputs sensitive to contact closure, optional built-in Power over Ethernet (POE), dual DC power.
- 4 Remote 1-Wire Sensors over IP
- E-1W(P): two RJ11 connectors for daisy chaining many 1-wire temperature/humidity/dew point, thermocouple, or digital input expanders in any combination (up to 24 single-reading 1-wire sensors); two digital inputs sensitive to contact closure; dual DC power; optional Power over Ethernet (POE).
- Use an RJ45 RS485 Sensor Expander to add 8 RJ45 RS485 sensors.
- Use a Digital Input/Output Expander to add 16 digital inputs and 16 digital outputs.
- Four output relays for control of external devices.
- Relay activates upon alarm or via the user interface.
- Control output relays via SNMP SET commands to power on/off external devices.
- Supports NTI’s IP network video cameras for live view of any facility.
- One integrated view – see different Web cameras side-by-side with physical and environmental parameters.
- Any programmed event can trigger a snapshot from an IP camera.
- Monitor (ping) up to 64 IP network devices.
- Alerts are sent if devices are not responding
- Linux inside.
- Create multiple alerts for any installed sensor.
- Sensor conditions (events) can be configured to trigger alerts by themselves, and/or be used in combination with other events to trigger Smart Alerts.
- Configure up to 50 events.
- Setup SSH commands to be sent when events are triggered to soft shutdown or reboot machines.
- Up to 20 Smart Alerts can be configured to use different event combinations to send alert messages.
- Configure up to 50 events.
- View entries stored in the system logs.
- Event log records system events such as alerts, user login/logout, failed email messages, etc.
- Data log records samples of sensor readings. User specified sampling time period.
- With E-16D, up to 1,724 data log entries and 1,000 event log entries are stored.
- With E-16DEL, up to 1,200,000 data log entries and 3,000 event log entries are stored.
- 256 MB non-volatile memory – both the data log and event log persist after power cycle.
- Automatically configures network settings received from a connected DHCP server.
- If a DHCP server is not found, the default static IP address will be used.
- Integrates with various Open Source monitoring packages – Nagios and MRTG.
- The unit can be polled via SNMP.
- USB ports for connecting USB modem or for downloading log data to USB flash drive.
- Internal battery backup.
- Alerts are sent when there is a power outage and when power returns.
- Available with optional dual power for connection to two separate power sources.
- Up to five units can be connected via Ethernet connection or using CAT5 expansion cables to increase the number of sensors connected.
- Cascade up to four E-2D/5D/16D units as slaves to one E-2D/5D/16D master unit via Ethernet connection.
- Each master and slave unit needs its own unique IP address.
- Cascade up to four E-16D units as slaves to one E-16D master unit using CAT5/5e/6 patch cables with RJ45 connectors wired straight through.
- Each slave unit needs its own unique RS485 address value that can range from 1-255.
- Uses a single Web interface for all systems/sensors connected.
- Cascade up to four E-2D/5D/16D units as slaves to one E-2D/5D/16D master unit via Ethernet connection.
- Available with optional 48VDC or 24VDC power.
- Optional Self-Hosted Enterprise Environment Monitoring System Management Software for monitoring and configuring up to 3,000 E-2D/5D/16D/MICRO/1W devices and all connected sensors. Access from anywhere using a web browser on a computer, smartphone, and/or tablet. No clients or special apps to install.
- 1RU rack mount case is standard.
- The ENVIROMUX system can be mounted so that the sensor connectors are facing the front or back of the rack.
- Security: HTTPS, SSHv2, SSLv3, IP Filtering, LDAPv3, AES 256-bit encryption, 16-character username/password authentication, user account restricted access rights.
- Multi-language support – English, German, Chinese, and Japanese.
- Use in data centers, co-lo sites, web hosting facilities, telecom switching sites, POP sites, server closets, or any unmanned area that needs to be monitored.
- Use the E-16D with a wireless router and Wi-Fi Range Extender to create a Wireless Environment Monitoring System.
- Configure, monitor, and receive alerts without the use of a wired network connection.
1. Power Port
- 100 to 240 VAC at 50 or 60 Hz via IEC connector. (Country-specific power supply cable included.)
- Power consumption: 35W
- Connection for Earth Ground.
- Fuse protection.
- Optional 48VDC power (not shown).
- Accepts 36~72VDC (48VDC nominal).
- Optional 24VDC power (not shown).
- Accepts 20~32VDC (24VDC nominal).
- Optional dual power (not shown).
- Available on AC, 48VDC, and 24VDC models.
- If the first power source fails, the unit will automatically, without interruption, switch over to the second power source before switching to the battery backup.
2. RJ45 Sensor Ports
- Sixteen RJ45 modular jacks for connecting NTI temperature, humidity, temperature/humidity, liquid detection, smoke detection, glass break, vibration and motion sensors.
3. Digital Inputs
- Eight screw terminals pairs for connecting dry contact devices.
- Input voltage: 0VDC to +25VDC.
- Provides +12VDC, 50mA for terminals 1-7, and +12VDC, 350mA for terminal 8 only.
- Fuse protection.
4. Digital Outputs
- Four screw terminals pairs.
- Potential-free relay switch contacts.
- Normally open / normally closed connection points.
- Maximum switching load: 0.5A at 100VAC, 1A at 30VDC, 0.5A at 48VDC.
5. Beacon Port
- One screw terminal pair.
- Provides +12VDC, 180 mA to supply an alarm beacon.
- Fuse protection
6. Siren Port
- One screw terminal pair.
- Provides +12VDC, 180 mA to supply a siren.
- Fuse protection
7. AUX Power
- One screw terminal pair.
- Provides 12VDC, 150mA.
8. USB Device Ports
- Four female USB Type A connectors for connecting USB modem or for downloading log data to USB flash drive.
- Two USB ports on front panel and 2 on back panel.
9. USB Console Port
- One female USB Type B connector for connecting a PC for serial terminal access.
10. RS232 (DCS) Port
- One female RJ45 serial port for terminal access.
11. Ethernet Port
- One 10/100 Base-T Ethernet port with RJ45 Ethernet connector.
- Supports full- and half-duplex.
12. RS232 AUX Port
- One RJ45 port for connecting a serial GSM modem or a remote serially-controlled device.
13. Cascade In/Out Ports
- Two RJ45 jacks.
- A maximum of 5 systems can be used in a cascaded configuration via RS485 to increase the number of sensor ports (1 master, 4 slaves).
- Each slave unit needs its own unique RS485 address value that can range from 1-255.
- Use CAT5/5e/6 patch cables with RJ45 connectors wired straight through
- Up to 4,000 feet between the master unit and the slave unit.
- The last slave must have a terminating plug (E-TRMPLG, not included) in the empty socket.
- Uses a single Web interface for all systems connected.
Protocols
- HTTP/HTTPS, SNMP V1/V2c/V3, SMTP, TCP/IP, Syslog, SNTP, DHCP, SSHv2, SSLv3, TLS v1.2, LDAPv3, XOAUTH2, AES 256-bit, 3DES, Blowfish, RSA, EDH-RSA, Arcfour, IPV6, WAP 2.0, RADIUS
- Support for XOAUTH2 provides higher security authentication for email accounts (e.g. Gmail).
- Compatible with any SNMP management software.
- The unit can be polled via SNMP.
- Operates and configures via HTTP/HTTPS web page, Telnet, SSH, or USB/RJ45 serial interface.
- Supports Internet Explorer 6.0 and higher, Firefox 1.5 and higher, Netscape 9, Google Chrome, Safari 1.3 and higher for MAC, and Safari 3.0 and higher for PC.
- Multiplatform support: Windows 7/8/10, Windows Server 2008/2012/2016/2019, Solaris, Linux, FreeBSD, and MAC OS 10/11.
- An IP address can be assigned to the E-16D automatically by a DHCP server.
- Generates SNMP traps, email alerts, syslog messages, and SMS messages (via USB 3G modem).
- Alerts are posted in event log, which is accessible through Web user interface.
- Email alerts can be sent to 17 addresses.
- Users can configure the schedule for when they will be alerted, as well as customize the e-mail subject line for each sensor alert.
- SNMP traps have unique OID’s (Object Identifiers) for each sensor.
- Supports HTTP REST API to poll sensor data with response in JSON format.
Internal Temperature Sensor
- For monitoring the temperature inside the E-16D case.
- Use an external temperature sensor for monitoring ambient air temperature.
- Applications from 32 to 104°F (0 to 40°C).
- Temperature accuracy:
- ±1.44°F (±0.8°C) for 32 to 41°F (0 to 5°C).
- ±0.72°F (±0.4°C) for 41 to 104°F (5 to 40°C).
Internal Humidity Sensor
- For monitoring the humidity inside the E-16D case.
- Use an external humidity sensor for monitoring humidity in the air.
- Applications from 20% to 80% relative humidity at temperatures between 32 to 104°F (0 to 40°C).
- Accurate to within ±3% relative humidity (at 77°F/25°C).
Internal Power Sensor
- Measures mains voltage: 0 to 255 VAC
- Measures battery voltage: 0 to 20 VDC
- Measures voltage on 24VDC models: 20 to 32VDC
- Measures voltage on 48VDC models: 36 to 72VDC
- Alerts are sent when there is a power outage and when power returns.
Back-up Battery
- Rechargeable sealed lead-acid battery.
- Provides back-up for one hour.
NTI Part # | Hours |
---|---|
E-16D | 89,884 |
E-16DDP | 107,046 |
E-16D-24V | 115,143 |
E-16D-24VDP | 121,484 |
E-16D-48V | 115,143 |
E-16D-48VDP | 121,484 |
E-16DEL | 89,884 |
Dimensions
- WxDxH (all options):
- Without supplied rackmount kit: 16.19×10.01×1.75″
- With supplied rackmount kit: 19×10.01×1.75″
Weight
- E-16D: 9.5 lb (4.31 kg).
- E-16D-48VDP: 9.6 lbs (4.36 kg).
Environmental
- Operating temperature: 32 to 104°F (0 to 40°C).
- Storage temperature: -22 to 140°F (-30 to 60°C).
- Operating/Storage Relative Humidity: 5 to 90% non-condensing RH.
Regulatory Approvals
- CE, RoHS
- TAA compliant
Web Interface
- Configuration can be done over the Internet/LAN or 4G data connection via Web page.
- 4G data connection requires a USB 4G modem with a data plan.
- Email and SMS alerts can be sent through the modem instead of the Ethernet connection.
- 4G data connection requires a USB 4G modem with a data plan.
- Supports Internet Explorer 6.0 and higher, Firefox 1.5 and higher, Netscape 9, Google Chrome, Safari 1.3 and higher for MAC, and Safari 3.0 and higher for PC.
- Configure sensor thresholds, alarm methods, formats of alerts, and system data log.
- Customize SMS messages and email subject headers for sensor alerts.
- View/edit sensors’ current values, thresholds and alert statuses.
- All sensors connected, including up to 8 Remote Temperature/Humidity Sensors over IP, to the E-16D can be viewed on one summary page.
- All sensors in alert can be quickly viewed on the alert summary page to enable timely responses.
- User configurable settings allow sensors to return to normal status when alert condition clears, without manually acknowledging/dismissing the alert.
- View entries stored in the system logs.
- Event log records system events such as alerts, user login/logout, failed email messages, etc.
- Data log records samples of sensor readings. User specified sampling time period.
- With E-16D, up to 1,724 data log entries and 1,000 event log entries are stored.
- With E-16DEL, up to 1,200,000 data log entries and 3,000 event log entries are stored.
- 256 MB non-volatile memory – both the data log and event log persist after power cycle.
- The log can be downloaded as a tab-delimited plain text file.
- Configure IP information (address, subnet mask, default gateway, DNS, etc.), user administrative settings, and data logging settings.
- Upload custom x509 certificates.
- Up to 16 users can access the web page at one time.
- Permissions, schedule and alert methods are configurable for each user.
- Configure up to 50 sensor conditions (events).
- Configure up to 20 Smart Alerts to use different event combinations to send alert messages.
- Up to five units can be used together to increase the number of sensors connected.
- Cascade up to four E-2D/5D/16D units as slaves to one E-2D/5D/16D master unit via Ethernet connection.
- Each master and slave unit needs its own unique IP address.
- IP sensors can only be connected to a master unit.
- E-16D slave units can also be configured as RS485 local slave units using CAT5/5e/6 patch cables with RJ45 connectors wired straight through.
- Each slave unit needs its own unique RS485 address value that can range from 1-255.
- The last slave must have a terminating plug (not included) in the empty socket.
- Uses a single Web interface for all systems/sensors connected.
- Cascade up to four E-2D/5D/16D units as slaves to one E-2D/5D/16D master unit via Ethernet connection.
- Multi-language support – English, German, Chinese, and Japanese.
Front Panel Interface
- LEDs indicate the following:
- “INT ALERT” – internal sensor goes out of range of a configurable threshold.
- “EXT ALERT” – external sensor goes out of range of a configurable threshold.
- “LOW BAT” – backup battery is low.
- “CHECK LOG” – message is posted to the log.
- “AUX” – indicates Auxiliary device is powered.
- “PWR” – indicates system is powered.
- Alarm Test/Silence button – use to test or silence the alarm connected to the siren terminals
- Restore Defaults button – use to manually restore the E-16D back to factory settings.
- System Reset button – use to manually reboot/restart the firmware for the E-16D.
Serial Interface / Telnet / SSH
- Configure, control and monitor over the text-based menu system accessible via USB console port, RJ45 serial port, Telnet, and SSH.
- Serial baud rate: 9,600 to 115,200bps.
- Data format: 1 start bit, 8 data bits, no parity, 1 stop bit.
- Access is controlled via username/password.
- System stores encrypted login information.
- Two user levels: user and administrator.
- Multi-language support – English, German, Chinese, and Japanese.
- Telnet and SSH can be enabled or disabled.
- Network Security Enhancement: Disabling Telnet can prevent unsecure text menu access to the E-16D.
Network Operation
- Automatically configures network settings received from a connected DHCP server.
- If a DHCP server is not found, the default static IP address will be used.
- SNMP support, allowing integration into network management platforms.
- Control output relays via SNMP SET commands to power on/off external devices.
- SET command can be sent from SNMP software, MIB browser (Windows), or command line (Linux).
- Control output relays via SNMP SET commands to power on/off external devices.
- Updating the system firmware.
Open Source Monitoring Integration
- SNMP Plugin for Nagios
- NTI SNMP Plugin for Zabbix
- Using Multi Router Traffic Grapher (MRTG).
- Data Logging using Syslog
Optional Management Software
- Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 ENVIROMUX units and all connected sensors.
- Push configuration changes to multiple connected units in a group at once.
- E.g. new users, mail server, network settings, security settings, system settings, etc.
- Choose between:
- E-MNG-SH Self-Hosted Enterprise Software for monitoring and configuring up to 3,000 E-2D/5D/16D, E-MICRO-TRH(P), E-1W(P) devices and all connected sensors. Access from anywhere using a web browser on a computer, smartphone, and/or tablet. No clients or special apps to install.
- E-MNG-xxx0 Enterprise Software – Client/Server Architecture for monitoring and configuring up to 3,000 E-2D/5D/16D, E-MICRO-TRH(P), E-1W(P) units and all connected sensors. Requires Java.
Mobile Summary Page
- View summary page on mobile devices – smartphones, tablets, etc.
- Summary page lists all connected sensors’ current values and alert statuses.
PDF Documentation
- E-16D/-16DEL Data Sheet
- E-16D/-16DEL Installation & Operation Manual
- E-16D/-16DEL Quick Installation Guide
- E-16D/-16DEL Serial Control Manual
- Environmental Sensors
- Alert & Communication Accessories
- Motion/Intrusion/Vibration Sensors
- Power Relay Sensors
- Sensor Accessories
- Replacement Back-up Battery
- How To – Configure Router for Remote Access ENVIROMUX
- How To – Locating OIDs Using a MIB Browser
- How To – Send SMS Messages to 18-34 Users
- How To – Install Console Drivers On Windows 8 Computer for E-16D
- How To – Calibrate the Internal Humidity Sensor
- How To – Use LDAP Server with the E-16D
- How To – Setup Syslog in an ENVIROMUX Enterprise Environment Monitoring System
- How To – Restore Defaults via RS232
- How To – Remove and Dispose Back-up Battery
- How To – Create an x.509 Certificate
- How To – Install E-LD to E-xD Using Connection to USB Console
3D Model
Please note that Sensors & Accessories are Sold Seperately. Click on Sensor Type below for More Information
Environmental Sensors
- Remote Temperature/Humidity Sensor over IP
- Temperature Sensors
- RTD Temperature Transmitters/Sensors
- Temperature/Humidity Sensors
- Industrial Temperature/Humidity Sensors
- Rope-Style Leak Detectors
- Leak Location Detection Sensors
- Spot Leak Detectors
- Under Carpet & Tape-Style Detectors
- Liquid Level Float Switches
- Ultrasonic Level Transmitter
- Smoke Detectors
- Gas Detectors
- Dust Detectors
- Air Flow/Velocity Detectors
- Outdoor Temperature Sensor
- Wind Speed Sensor
- Barometric Pressure Transmitter
- Pressure Sensors
- Noise Level Sensor
Security Sensors & Access Control
Power Relays & Sensors
- Power Over Ethernet Adapters
- AC Voltage Detectors
- AC & DC Power Monitors
- Hall-Effect Sensors
- 3-Phase Power Monitors
- Current Transformers
Alert & Communication Accessories
Sensor Accessories
- Programmable LED Sensor Display
- RJ45 RS485 Sensor Expander
- Digital Input/Output Expanders
- RS485/RS232/RS422 to Fiber Converter/Extender
- Sensor Converters – 4-20mA, 5VDC
- WiFi Range Extender
- Sensor Cables
- Surge Protectors
- Intrinsically Safe Barrier
Optional Extension Rail Kit
- Use to mount up to 6 sensor adapters to the E-16D.
- Space-saving design. Uses the extra rackmounting space behind the E-16D.
- Allows adjustments to various rack depths from 19″ (483 mm) to 29.5″ (749 mm).
NTI Part # | Power | Logging |
---|---|---|
E-16D | AC | 1,000 data log entries; 1,000 event log entries |
E-16DDP | Dual AC | 1,000 data log entries; 1,000 event log entries |
E-16D-24V | 24VDC | 1,000 data log entries; 1,000 event log entries |
E-16D-24VDP | Dual 24VDC | 1,000 data log entries; 1,000 event log entries |
E-16D-48V | 48VDC | 1,000 data log entries; 1,000 event log entries |
E-16D-48VDP | Dual 48VDC | 1,000 data log entries; 1,000 event log entries |
E-16DEL | AC | 1,200,000 data log entries; 3,000 event log entries |
All Products In This Category
ENVIROMUX
ENVIROMUX-2D
Small Enterprise Environment Monitoring System
E-MNG-SH
Self-Hosted Enterprise Environment Monitoring System Management Software
ENVIROMUX-5D
Medium Enterprise Environment Monitoring System
E-MNG
Management Software for Enterprise Environment Monitoring Systems – Client/Server Architecture
ENVIROMUX-16D/-16DEL
Large Enterprise Environment Monitoring System
E-MNG-LC
Management Software for Low-Cost Environment Monitoring Systems
ENVIROMUX-MICRO-T/-TRHP
Micro Environment Monitoring System
IPDU-S2
Secure Remote Power Control Unit with Environmental Monitoring
ENVIROMUX-MINI-LXO
Mini Environment Monitoring System
PWR-RMT-RBT-LC
Low-Cost Remote Power Reboot Switch with IEC320 C13 Outlet
ENVIROMUX-1W
Low-Cost Environment Monitoring System
PWR-RMT-RBT2-515R-LCV2
Low-Cost 2-Port Remote Power Reboot Switch with NEMA 5-15R Outlets