E-MICRO-T/-TRHP
Micro Environment Monitoring System
Monitor and manage server room environmental and security conditions over IP. Provides early warnings before critical events turn into disaster.
Also known as: Remote SNMP Environment Monitoring System, EMS, monitor networking closets, server room alert, IP temperature sensor, humidity sensor, computer room humidity probe.
Product Code: E-MICRO-T/-TRHP ( also known as ENVIROMUX MICRO-T/-TRHP )
Warranty: 12 month Standard Warranty
The ENVIROMUX® Micro Environment Monitoring System (EMS) monitors critical environmental conditions, such as temperature, humidity, liquid water presence, power, intrusion, and smoke. When a sensor goes out of range of a configurable threshold, the system will notify you via email, web page, network management (SNMP), and/or SMS messages (via email-to-SMS).
The system functions independently or as an IP-connected remote sensor for the E-2D/5D/16D. It features an integrated temperature/humidity sensor, two RJ45 sensor ports for external temperature/humidity sensors, two dry contact inputs and optional built-in Power over Ethernet (PoE).
- Sensors supported by a single E-MICRO:
- 1 integrated temperature/humidity combination sensor
- 2 RJ45 ports for external temperature/humidity sensors
- 2 digital inputs sensitive to contact closure.
- Dual DC power provides dual redundancy.
- Available with optional built-in Power over Ethernet.
- Sensors are hot pluggable.
- Monitor (ping) up to 4 IP network devices – alerts are sent if devices are not responding.
- Create multiple alerts for any installed sensor.
- Sensor conditions can be configured to trigger alerts by themselves, and/or be used in combination with other alerts to trigger one Smart Alert.
- Configure up to 32 alerts, and one Smart Alert.
- Alerts are posted in message log, which is accessible through Web user interface.
- Supports NTI’s IP network video cameras for live view of any facility.
- Integrates with various Open Source SNMP monitoring packages – Nagios.
- The unit can be polled via SNMP.
- Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 ENVIROMUX units and all connected sensors.
- Optional Android App provides an easy-to-use interface for monitoring sensor statuses and acknowledging/dismissing sensor alerts from an unlimited number of E-MICRO units.
- Security: HTTPS, TLS v1.2, AES 256-bit encryption, 16-character username/password authentication, user account restricted access rights.
- Integrated mounting brackets for easy surface/wall mounting.
- Optional DIN mounting available.
- Use in data centers, co-lo sites, web hosting facilities, telecom switching sites, POP sites, server closets, or any unmanned area that needs to be monitored.
- Use the E-MICRO-TRH(P) with a wireless router and Wi-Fi Range Extender to create a Wireless Environment Monitoring System.
- Configure, monitor, and receive alerts without the use of a wired network connection.
RJ45 Sensor Ports
- Two RJ45 modular jacks for connecting temperature sensors or combined temperature/humidity sensors.
- Three levels of user-defined alerts – normal, warning, critical.
Dry Contact Closures
- Two screw terminal pairs for connecting dry contact devices and the liquid detection sensor.
USB Port
- One female Micro USB connector – reserved for future use.
Ethernet Port
- One female RJ45 connector.
- 10/100 Base-T Ethernet interface.
Protocols
- HTTP/HTTPS, SNMP V1/V2c/V3, SMTP, TCP/IP, Syslog, SNTP, DHCP, TLS v1.2, AES 256-bit, 3DES, Blowfish, RSA, EDH-RSA, Arcfour.
- Compatible with any SNMP management software.
- The unit can be polled via SNMP.
- Operates and configures via HTTP/HTTPS web page.
- Supports Microsoft Edge, Internet Explorer 6.0 and higher, Firefox 1.5 and higher, Google Chrome, and Safari 1.3 and higher (for MAC).
- Multiplatform support: Windows 7/8/10/11, Windows Server 2008/2012/2016/2019/2022, Solaris, Linux, FreeBSD, and MAC OS 10/11/12.
- An IP address can be assigned to the E-MICRO automatically by a DHCP server.
- Generates SNMP traps, email alerts, syslog messages, and SMS messages (via email-to-SMS).
- Alerts are posted in event log, which is accessible through Web user interface.
- Email alerts can be sent to 9 addresses.
- Users can configure the schedule for when they will be alerted.
- Supports HTTP REST API to poll sensor data with response in JSON format.
Integrated Temperature/Humidity Sensor
- Applications from -4 to 167°F (-20 to 75°C) and 0 to 90% relative humidity.
- Temperature accuracy
(in moving air – minimum airflow 8.2 ft/s (2.5 m/s)):- ±1.44°F (±0.8°C) for -4 to 41°F (-20 to 5°C).
- ±0.72°F (±0.4°C) for 41 to 140°F (5 to 60°C).
- ±1.62°F (±0.9°C) for 140 to 167°F (60 to 75°C).
- Resolution: 0.2°F (0.1°C).
- Humidity accuracy (at 77°F/25°C)
- 0 to 10% RH: ±5%
- 10 to 20% RH: ±4%
- 20 to 80% RH: ±3%
- 80 to 90% RH: ±4%
Dimensions
- WxDxH in (all options): 4×3.44×1.37 (102x87x35 mm).
- Includes mounting holes to match rack hole spacing.
Power
- E-MICRO-TRH:
- Dual DC power provides dual redundancy.
- If the first power source fails, the unit will automatically, without interruption, switch over to the second power source.
- The unit draws power from the source with the highest DC voltage (nominal 5.5V).
- If both sources have exactly the same voltage, it will draw in part from each of them.
- 100 to 240 VAC at 50 or 60 Hz via AC adapter.
- Includes one country-specific AC adapter. The second AC adapter is sold separately (PWR-SPLY-ELC).
- Input voltage: 5.5VDC ±5%
- Power consumption: 4W max.
- Dual DC power provides dual redundancy.
- E-MICRO-TRHP:
- Built-in Power over Ethernet and dual DC power provides triple redundancy.
- Power over Ethernet standards supported: IEEE 802.3af, 802.3at.
- Proprietary schemes such as Cisco Discovery Protocol are not supported.
- Similar legacy switches and routers will have to use PWR-SPLY-ELC.
- Proprietary schemes such as Cisco Discovery Protocol are not supported.
- Power over Ethernet standards supported: IEEE 802.3af, 802.3at.
- If the first power source fails, the unit will automatically, without interruption, switch over to the second power source.
- The unit draws power from the source with the highest DC voltage (nominal 5.5V).
- If two or more sources have exactly the same voltage, it will draw in part from each of them.
- 100 to 240 VAC at 50 or 60 Hz via AC adapter (not included).
- Country-specific AC adapters sold separately (PWR-SPLY-ELC).
- Input voltage: 5.5VDC ±5%
- Power consumption: 4W max.
- Built-in Power over Ethernet and dual DC power provides triple redundancy.
- Use the PWR-48V-5-5V4A DC-DC power converter to install the E-MICRO in a 48V or 24V Telecom environment.
MTBF
- E-MICRO-TRH: 628,394 hours.
- E-MICRO-TRHP: 577,812 hours.
Environmental
- Operating & Storage Temperature: -4 to 167°F (-20 to 75°C).
- Operating & Storage Relative Humidity: 0 to 90% non-condensing RH.
Regulatory Approvals
- CE, RoHS.
Web Interface
- Configuration can be done over the Internet/LAN via Web page.
- When connected as an IP remote sensor for an E-2D/5D/16D unit, the E-MICRO is configured via the E-xD web interface.
- Supports Microsoft Edge, Internet Explorer 6.0 and higher, Firefox 1.5 and higher, Google Chrome, and Safari 1.3 and higher (for MAC).
- Configure sensor thresholds, alarm methods, formats of alerts, and system data log.
- View/edit sensors’ current values, thresholds and alert statuses.
- All sensors connected to the E-MICRO can be viewed on one summary page.
- User configurable settings allow sensors to return to normal status when alert condition clears, without manually acknowledging/dismissing the alert.
- View/edit entries stored in the system logs.
- Event log records system alerts.
- Stores up to 200 entries.
- Data log records samples of sensor readings per minute.
- Stores up to 43,000 entries per sensor.
- The data log can be downloaded as a comma-separated plain text file.
- Configure IP information (address, subnet mask, default gateway, DNS, etc.), user administrative settings, and data logging settings.
- Up to 9 users can access the web page at one time.
- Permissions, schedule and alert methods are configurable for each user.
- Configure up to 32 sensor conditions (alerts).
- Configure 1 Smart Alert to use different alert combinations to send alert messages.
Telnet
- Monitor over the text-based menu system accessible via Telnet.
- Access is controlled via username/password.
- System stores encrypted login information.
- Two user levels: user and administrator.
- Telnet can be enabled or disabled.
- Network Security Enhancement: Disabling Telnet can prevent unsecure text menu access to the E-MICRO.
Network Operation
- SNMP support, allowing integration into network management platforms.
- Updating the system firmware.
Open Source Monitoring Integration
HTTP REST API
- Supports HTTP REST API to poll sensor data with response in JSON format
Optional Management Software
- Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 ENVIROMUX units and all connected sensors.
- Push configuration changes to multiple connected units in a group at once.
- E.g. new users, mail server, network settings, security settings, system settings, etc.
- Choose between Enterprise Management Software or Low-Cost Management Software.
- E-MNG-SH Self-Hosted Enterprise Software for monitoring and configuring up to 3,000 E-2D/5D/16D, E-MICRO-TRH(P), E-1W(P) devices and all connected sensors. Access from anywhere using a web browser on a computer, smartphone, and/or tablet. No clients or special apps to install.
- E-MNG-xxx0 Enterprise Software – Client/Server Architecture for monitoring and configuring up to 3,000 E-2D/5D/16D, E-MICRO-TRH(P), E-1W(P) units and all connected sensors. Requires Java.
- E-MNG-LC Low-Cost Management Software for monitoring and configuring up to 3,000 E-MICRO-TRH(P) and E-1W(P) units and all connected sensors
Optional Android App for Tablet/Phone
- Optional Android App provides an easy-to-use interface for monitoring sensor statuses and acknowledging/dismissing sensor alerts from an unlimited number of E-MICRO units.
PDF Documentation
- E-16D/-16DEL Data Sheet
- E-16D/-16DEL Installation & Operation Manual
- E-16D/-16DEL Quick Installation Guide
- E-16D/-16DEL Serial Control Manual
- Environmental Sensors
- Alert & Communication Accessories
- Motion/Intrusion/Vibration Sensors
- Power Relay Sensors
- Sensor Accessories
- Replacement Back-up Battery
- How To – Configure Router for Remote Access ENVIROMUX
- How To – Locating OIDs Using a MIB Browser
- How To – Send SMS Messages to 18-34 Users
- How To – Install Console Drivers On Windows 8 Computer for E-16D
- How To – Calibrate the Internal Humidity Sensor
- How To – Use LDAP Server with the E-16D
- How To – Setup Syslog in an ENVIROMUX Enterprise Environment Monitoring System
- How To – Restore Defaults via RS232
- How To – Remove and Dispose Back-up Battery
- How To – Create an x.509 Certificate
- How To – Install E-LD to E-xD Using Connection to USB Console
3D Model
Please note that Sensors & Accessories are Sold Seperately. Click on Sensor Type below for More Information
Environmental Sensors
- Temperature/Humidity Sensors
- Rope-Style Leak Detectors
- Spot Leak Detectors
- Under Carpet & Tape-Style Leak Detectors
- Liquid Level Float Switches
- Smoke Detectors
- Gas Detectors
- Air Flow Sensor
Security Sensors
Communication Accessories
Power Sensors
Sensor Accessories
- WiFi Range Extender
- Sensor cables
- Self-Adhesive Clips for Liquid/Chemical Sensor Rope
- Surge Protectors
NTI Part # | Description |
---|---|
E-MICRO-TRH | Micro Environment Monitoring System, Integrated Temp/Humidity Sensor. One power supply included. |
E-MICRO-TRHP | Micro Environment Monitoring System, Integrated Temp/Humidity Sensor, POE. Power supply NOT included |
E-MICRO-TRH-D | Micro Environment Monitoring System, Integrated Temp/Humidity Sensor, DIN Mounted. One power supply included |
E-MICRO-TRHP-D | Micro Environment Monitoring System, Integrated Temp/Humidity Sensor, POE, DIN Mounted. Power supply NOT included |
E-MICRO-TRH-TAA | Micro Environment Monitoring System, Integrated Temp/Humidity Sensor. One power supply included. TAA compliant. |
E-MICRO-TRHP-TAA | Micro Environment Monitoring System, Integrated Temp/Humidity Sensor, POE. Power supply NOT included. TAA compliant. |
All Products In This Category
ENVIROMUX
ENVIROMUX-2D
Small Enterprise Environment Monitoring System
E-MNG-SH
Self-Hosted Enterprise Environment Monitoring System Management Software
ENVIROMUX-5D
Medium Enterprise Environment Monitoring System
E-MNG
Management Software for Enterprise Environment Monitoring Systems – Client/Server Architecture
ENVIROMUX-16D/-16DEL
Large Enterprise Environment Monitoring System
E-MNG-LC
Management Software for Low-Cost Environment Monitoring Systems
ENVIROMUX-MICRO-T/-TRHP
Micro Environment Monitoring System
IPDU-S2
Secure Remote Power Control Unit with Environmental Monitoring
ENVIROMUX-MINI-LXO
Mini Environment Monitoring System
PWR-RMT-RBT-LC
Low-Cost Remote Power Reboot Switch with IEC320 C13 Outlet
ENVIROMUX-1W
Low-Cost Environment Monitoring System
PWR-RMT-RBT2-515R-LCV2